Which heat shrink tubing do you need? This guide explains every type used in power cable work — thin wall, medium wall and heavy wall, adhesive-lined dual wall, bus bar, anti-tracking and stress control tubing — with shrink ratios, temperature ranges, a simple 3-step size calculation, worked examples, installation tips and FAQs.
Quick Answer: How Do You Choose Heat Shrink Tubing?
Choose heat shrink tubing in three steps:
1. Pick the type for the job — insulation, waterproof sealing, bus bar insulation, outdoor HV protection or stress control (see the table below). 2. Pick the shrink ratio — 2:1 for uniform objects, 3:1 for connectors and uneven shapes, 4:1 for the widest diameter variation. 3. Pick the size — the tube's supplied (expanded) diameter must be larger than the largest part you are covering, and its recovered (fully shrunk) diameter must be smaller than the smallest part, so it shrinks tight everywhere.
For example, to cover a cable of 14 mm with a crimped lug barrel of 28 mm, you need a tube that is at least about 31 mm supplied and no more than about 12 mm recovered — a 3:1 tube does this; a 2:1 tube cannot.
Vikram Power Technologies Pvt. Ltd. (VIKCHEM), Yamuna Nagar, Haryana, has manufactured heat shrink tubing and power cable accessories since 1988 for DISCOMs, switchgear OEMs, EPC contractors and industries in India and 20+ countries.
---
What Is Heat Shrink Tubing?
Heat shrink tubing is a cross-linked polymer tube that is expanded during manufacture and shrinks back to its original size when heated (typically with a gas torch or hot-air gun). It conforms tightly to cables, joints, lugs and bus bars to provide:
- ●Electrical insulation
- ●Moisture and environmental sealing (adhesive-lined types)
- ●Mechanical and abrasion protection
- ●Colour coding of phases
- ●Electric field control (stress control tubing at MV terminations)
- ●Clean and degrease the surface first — dirt and grease stop adhesive from bonding.
- ●Slide the tube on before crimping lugs or connectors if it will not pass over them afterwards.
- ●Use a soft yellow flame (or hot-air gun) and keep it moving — never a sharp blue flame held in one spot.
- ●Shrink from the centre outwards (or from one end) to push out trapped air.
- ●Watch the adhesive — on adhesive-lined tubes, heat until a small bead of adhesive appears at both ends.
- ●Let it cool before bending or moving the cable.
- ●Heat Shrink Insulating Tubing | Medium Wall Tubing | Heavy Wall Tubing
- ●Bus Bar Tubing | Dual Wall Tubing
- ●Anti-Tracking Tubing | Stress Control Tubing
- ●Contact VIKCHEM for a Quotation
Heat shrink tubing is the building block of every heat shrink cable termination kit and cable jointing kit.
---
Types of Heat Shrink Tubing (Comparison Table)
| Type | Shrink Ratio | Main Use | Voltage | Operating Temp. |
|---|---|---|---|---|
| Thin wall insulating tubing | 2:1 / 3:1 | General insulation, repair, colour coding | LV, and as part of MV kits up to 36kV | –55°C to +125°C |
| Medium wall tubing (adhesive lined) | 3:1 | Waterproof sealing of cable ends and connectors | LV and MV | –55°C to +125°C |
| Heavy wall tubing (adhesive lined) | 4:1 | HV insulation, end capping, heavy mechanical protection | Up to 35kV | –55°C to +135°C |
| Dual wall tubing | 3:1 | Hermetic sealing of splices and underground joints | LV and MV | –55°C to +125°C |
| Bus bar tubing | 3:1 | Phase insulation of copper / aluminium bus bars | LV to 36kV switchgear | Up to +135°C class |
| Anti-tracking tubing | 3:1 | Outdoor MV / HV terminations, polluted areas | 6.6kV to 36kV | –55°C to +120°C |
| Stress control tubing | 3:1 | Electric field grading at the cable screen cut | 6.6kV to 36kV | –40°C to +130°C |
Values are typical for VIKCHEM products — see each product page for the full data sheet.
---
Shrink Ratio Explained: 2:1 vs 3:1 vs 4:1
The shrink ratio is the supplied diameter divided by the fully recovered diameter.
| Shrink Ratio | Supplied → Recovered | Best For |
|---|---|---|
| 2:1 | 20 mm → 10 mm | Uniform objects: wires, cores, colour coding |
| 3:1 | 30 mm → 10 mm | Connectors, lugs and joints where the diameter changes |
| 4:1 | 40 mm → 10 mm | Large diameter steps, irregular shapes, end caps |
A higher ratio covers a wider range of diameters with one tube, which means fewer sizes to stock and easier installation over large lugs and connectors.
---
How to Calculate the Right Tubing Size
Measure the largest diameter (D-max: usually the lug barrel, connector or joint) and the smallest diameter (D-min: usually the cable or core insulation) that the tube must cover.
Rule 1 — Supplied diameter: at least 10–15% bigger than D-max, so the tube slides on easily.
Rule 2 — Recovered diameter: smaller than D-min, so the tube grips tightly after shrinking.
Worked Examples
| Job | D-min | D-max | Tube needed (supplied / recovered) | Ratio |
|---|---|---|---|---|
| Insulating a 10 mm core | 10 mm | 10 mm | ≥ 12 mm / ≤ 9 mm | 2:1 works |
| Cable 14 mm with lug barrel 28 mm | 14 mm | 28 mm | ≥ 31 mm / ≤ 12 mm | 3:1 needed |
| Cable 15 mm with connector 45 mm | 15 mm | 45 mm | ≥ 50 mm / ≤ 13 mm | 4:1 needed |
Length: allow for a small lengthwise shrinkage (check the data sheet) and keep enough overlap onto the cable — typically at least 25–50 mm on each side of a sealed area for adhesive-lined tubes.
Wall thickness: the wall gets thicker after shrinking. Use the recovered wall thickness from the data sheet when checking insulation or clearance in a panel.
---
Bus Bar Tubing: Selecting for Switchgear
For bus bar insulation, measure the bus bar's width and thickness and calculate its perimeter (2 × width + 2 × thickness). Select a tube whose recovered circumference is smaller than the bus bar perimeter and whose supplied size slides over the bar (and any joints or bends). Use phase colours (red, yellow, blue, black) for easy identification. Bus bar tubing adds insulation but does not replace the required air clearances in the switchgear design — confirm with the panel standard and OEM.
---
Indoor vs Outdoor: Why Anti-Tracking Tubing Matters
Outdoors, rain, dust, salt and industrial pollution form a conductive film on the tube surface. Under voltage, this causes surface tracking — small carbon paths that grow until flashover. Anti-tracking tubing is formulated to resist tracking and UV, so it is used as the outer layer on outdoor 6.6kV to 36kV terminations. Indoors, standard non-tracking insulating tubing is normally sufficient. Read more in our 11kV termination kit guide.
---
How to Install Heat Shrink Tubing Correctly
Common heating mistakes are covered in why cable joints and terminations fail.
---
Frequently Asked Questions
Q: What is the difference between 2:1 and 3:1 heat shrink tubing? A 2:1 tube shrinks to half its supplied diameter; a 3:1 tube shrinks to one third. 3:1 tubing covers a wider range of diameters, so it is preferred over lugs, connectors and joints where the diameter changes.
Q: How do I choose the correct heat shrink tubing size? Choose a tube whose supplied diameter is 10–15% larger than the largest part to be covered, and whose fully recovered diameter is smaller than the smallest part. This ensures it slides on easily and shrinks tight everywhere.
Q: What is adhesive-lined (dual wall) heat shrink tubing used for? Adhesive-lined tubing has an inner hot-melt layer that flows when heated and seals out water. It is used on cable ends, splices, connectors and underground joints where moisture sealing is needed.
Q: Which heat shrink tubing is used for bus bars? Colour-coded bus bar heat shrink tubing, normally 3:1 ratio, is used to insulate copper and aluminium bus bars in LV and MV switchgear up to 36kV.
Q: What is anti-tracking heat shrink tubing? Anti-tracking tubing is formulated to resist surface tracking and UV, and is used as the outer insulation on outdoor medium and high voltage cable terminations from 6.6kV to 36kV, especially in polluted or coastal areas.
Q: What does stress control tubing do? Stress control tubing is semi-conductive. Placed over the cable screen cut at 6.6kV to 36kV terminations, it spreads the concentrated electric field and prevents partial discharge and breakdown. It is not needed on 1.1kV LT cables.
Q: What temperature does heat shrink tubing shrink at? Most polyolefin heat shrink tubing begins to shrink at roughly 120°C and fully recovers at higher temperatures; follow the product data sheet. A gas torch with a soft yellow flame or an industrial hot-air gun is used on site.
Q: Where can I buy heat shrink tubing in India? VIKCHEM (Vikram Power Technologies Pvt. Ltd.), Yamuna Nagar, Haryana, manufactures thin, medium and heavy wall heat shrink tubing, dual wall, bus bar, anti-tracking and stress control tubing. Contact sales@vptpl.com or +91-99966-30201.
---
Order Heat Shrink Tubing From VIKCHEM
Send us the application, diameters to be covered (D-min and D-max), voltage, indoor or outdoor, colour and quantity (in metres or pieces) — we will recommend the right tubing and send a quotation.
Related reading: Power Cable Accessories — Complete Guide | Kit Selection Chart | Heat Shrink vs Cold Shrink