How to select a 33kV heat shrink cable termination kit or straight-through joint kit — 3 core and single core, XLPE and PILC, 35 to 1200 sq mm, indoor and outdoor. Includes the 33kV size chart with VIKCHEM kit codes, why 33kV size bands differ from 11kV, earthed vs unearthed systems, kit contents, installation checks and FAQs for substations, solar and wind plants.
Quick Answer: Which 33kV Cable Kit Do I Need?
A 33kV cable termination kit or 33kV jointing kit is selected by:
- ●Cable type — XLPE or PILC (or an XLPE-to-PILC transition joint)
- ●Cores — 3 core (3C) or single core (1C); single core is very common at 33kV
- ●Conductor size — in sq mm, from 35 up to 1200 sq mm
- ●Application — indoor termination, outdoor termination, or straight-through joint
- ●33/11kV substations — incoming and outgoing feeders, transformer and VCB panel terminations
- ●Grid substation links — underground 33kV cables in cities where overhead lines are not possible
- ●Solar power plants — main power blocks, 33kV collector cables between inverter-duty transformers and the pooling substation (see our solar cable accessories guide)
- ●Wind farms — WTG transformer to collector substation cables
- ●Industries and data centres — 33kV incoming supply to large plants
- ●Metro and railway projects — receiving substations and traction supply
- ●19/33kV (earthed system) — for networks where the neutral is effectively earthed; the most common grade
- ●33/33kV (unearthed system) — for networks where an earth fault can persist, so each core may see full line voltage to earth; this cable has thicker insulation
- ●Stress control tubing and stress relief mastic — critical at 33kV, where field stress at the screen cut is highest
- ●Non-tracking insulating tubing for each core
- ●Rain sheds (outdoor kits)
- ●Breakout (spreader boot) for 3 core cables
- ●Sealing mastic and sealant for the crotch and lug barrels
- ●Earthing components for the copper screen and armour
- ●Cleaning materials and installation instructions
- ●Clean, smooth insulation — remove every trace of the outer semiconducting layer; do not nick or scratch the XLPE.
- ●Correct screen cut position — measure to the instruction sheet; the stress control tube must overlap the screen cut as specified.
- ●Smooth connector surface — file down crimp flashes on joints; sharp edges cause local stress and partial discharge.
- ●Even, complete shrinking — shrink from the centre outwards with a moving yellow flame; no cold spots or trapped air.
- ●Screen and armour continuity — every earth connection tight and clean so fault current has a safe path.
- ●Insulation resistance (IR) test with a suitable megger
- ●High-voltage withstand test — commonly VLF (very low frequency) testing for XLPE cables, as per the utility's specification
- ●Partial discharge (PD) test on critical circuits such as solar evacuation and substation links
- ●36kV Heat Shrinkable Termination Kits (XLPE)
- ●36kV Straight-Through Joint Kits (XLPE)
- ●36kV PILC Termination Kits | 36kV PILC Joint Kits
- ●Contact VIKCHEM for a Quotation
For example, a 33kV 3 core 300 sq mm XLPE cable needs VXI-33 (indoor termination), VXO-33 (outdoor termination) or VXS-33 (straight-through joint). A 33kV 1 core 630 sq mm XLPE cable needs VXIS-35, VXOS-35 or VXSS-35.
Important: 33kV size bands are not the same as 11kV. A 3 × 185 sq mm cable is in the 120–185 band at 11kV but in the 185–300 band at 33kV. Always use the 33kV chart below.
Vikram Power Technologies Pvt. Ltd. (VIKCHEM), Yamuna Nagar, Haryana, has manufactured IS 13573 certified 36kV heat shrinkable termination kits and 33kV straight-through joint kits since 1988 for utilities, transmission and EPC contractors, and solar and wind developers in India and 20+ countries.
---
Where 33kV Cables Are Used
33kV is India's main sub-transmission voltage. 33kV cable kits are used for:
---
33kV Heat Shrink Kit Size Chart — VIKCHEM Kit Codes
33kV XLPE Cable — 3 Core
| Cable Size (sq mm) | Indoor Termination | Outdoor Termination | Straight-Through Joint |
|---|---|---|---|
| 3 × 70 – 95 | VXI-31 | VXO-31 | VXS-31 |
| 3 × 120 – 150 | VXI-32 | VXO-32 | VXS-32 |
| 3 × 185 – 300 | VXI-33 | VXO-33 | VXS-33 |
| 3 × 400 | VXI-34 | VXO-34 | VXS-34 |
| 3 × 500 – 630 | VXI-35 | VXO-35 | VXS-35 |
33kV XLPE Cable — Single Core
| Cable Size (sq mm) | Indoor Termination | Outdoor Termination | Straight-Through Joint |
|---|---|---|---|
| 1 × 35 – 50 | VXIS-31 | VXOS-31 | VXSS-31 |
| 1 × 70 – 150 | VXIS-32 | VXOS-32 | VXSS-32 |
| 1 × 185 – 300 | VXIS-33 | VXOS-33 | VXSS-33 |
| 1 × 400 | VXIS-34 | VXOS-34 | VXSS-34 |
| 1 × 500 – 630 | VXIS-35 | VXOS-35 | VXSS-35 |
| 1 × 800 – 1200 | VXIS-36 | VXOS-36 | VXSS-36 |
33kV PILC Cable
| Cable Size (sq mm) | Indoor Termination | Outdoor Termination | Straight-Through Joint |
|---|---|---|---|
| 3 × 70 – 95 | VPI-31 | VPO-31 | VPS-31 |
| 3 × 120 – 150 | VPI-32 | VPO-32 | VPS-32 |
| 3 × 185 – 300 | VPI-33 | VPO-33 | VPS-33 |
| 3 × 400 | VPI-34 | VPO-34 | VPS-34 |
| 1 × 35 – 50 | VPIS-31 | VPOS-31 | VPSS-31 |
| 1 × 70 – 150 | VPIS-32 | VPOS-32 | VPSS-32 |
| 1 × 185 – 300 | VPIS-33 | VPOS-33 | VPSS-33 |
| 1 × 400 – 630 | VPIS-34 | VPOS-34 | VPSS-34 |
| 1 × 800 – 1200 | VPIS-35 | VPOS-35 | VPSS-35 |
See the PILC range: 33kV PILC termination kits and 33kV PILC straight-through joints.
33kV XLPE to PILC Transition Joints
| Cable Size (sq mm) | 33kV Transition Joint |
|---|---|
| 3 × 16 – 95 | VTSJ-31 |
| 3 × 120 – 185 | VTSJ-32 |
| 3 × 240 – 300 | VTSJ-33 |
| 3 × 400 – 500 | VTSJ-34 |
| 1 × 16 – 95 | VTSSJ-31 |
| 1 × 120 – 300 | VTSSJ-32 |
| 1 × 400 | VTSSJ-33 |
| 1 × 500 – 630 | VTSSJ-34 |
| 1 × 800 – 1200 | VTSSJ-35 |
For 11kV and 22kV codes, see the full kit selection chart or our 11kV termination kit guide.
---
33kV vs 36kV — What Do the Ratings Mean?
A 33kV system has a highest system voltage (Um) of 36kV. That is why 33kV cable accessories are often called 36kV kits — "33kV termination kit" and "36kV termination kit" refer to the same product class. VIKCHEM 33kV heat shrink kits are designed and type tested for 36kV maximum system voltage under IS 13573 / IEC 60502-4.
---
Earthed vs Unearthed 33kV Systems (19/33kV vs 33/33kV Cables)
In India, 33kV XLPE cables are made in two grades:
Because the insulation thickness and core diameter differ, always tell your supplier whether the cable is 19/33kV (E) or 33/33kV (UE) — it affects which kit fits the core. The grade is printed on the cable sheath.
---
Indoor vs Outdoor 33kV Terminations
| Feature | Indoor (VXI / VPI) | Outdoor (VXO / VPO) |
|---|---|---|
| Where used | 33kV VCB / switchgear panels, transformer cable boxes, indoor GIS-adjacent bays | Outdoor yards, DP structures, line-to-cable towers, outdoor transformer bushings |
| Rain sheds | Not normally required | Required — more sheds than at 11kV for higher creepage |
| Tubing | Non-tracking insulating tubing | UV-stabilised, anti-tracking tubing |
| Length | Shorter, suits cable boxes | Longer, because of sheds and creepage |
Check clearances: 33kV terminations are longer than 11kV terminations. Before ordering an indoor kit, measure the height available in the cable box and the phase-to-phase clearance — especially when 3 core cables must be spread to the bushings.
---
What Is Inside a 33kV Heat Shrink Termination Kit?
A typical 33kV XLPE termination kit includes:
A 33kV straight-through joint kit adds stress control and insulating tubes for each joint, a semiconducting outer layer, a copper mesh / screen continuity set, and an adhesive-lined outer jacket. Lugs and connectors are usually selected separately to match the conductor — see our power cable accessories range.
---
5 Installation Checks That Matter Most at 33kV
Most 33kV failures start with workmanship, not the kit. Our engineers focus on these five checks:
Step-by-step guidance: XLPE cable jointing procedure. Common faults to avoid: why cable joints and terminations fail.
---
Testing After Installation
After installing 33kV terminations or joints, utilities typically carry out:
Always follow the test voltage and duration in your utility or project specification.
---
Frequently Asked Questions
Q: Which kit is used for a 33kV 3 core 300 sq mm XLPE cable? A 33kV 3 core 300 sq mm XLPE cable falls in the 185–300 sq mm band: VIKCHEM VXI-33 for indoor termination, VXO-33 for outdoor termination and VXS-33 for a straight-through joint.
Q: Which kit is used for a 33kV single core 630 sq mm cable? Use the 500–630 sq mm single core band: VXIS-35 (indoor), VXOS-35 (outdoor) or VXSS-35 (straight-through joint) for XLPE cable.
Q: Is a 33kV termination kit the same as a 36kV termination kit? Yes. A 33kV system has a highest system voltage (Um) of 36kV, so 33kV cable accessories are designed and tested to 36kV. Both names refer to the same product class.
Q: Why are 33kV size bands different from 11kV? 33kV cables have thicker insulation, so the core diameter for the same conductor size is larger. The kit bands are set by the diameter range each tube can fit, so the sq mm bands shift. Always use the 33kV chart.
Q: Does it matter if the 33kV cable is earthed (19/33kV) or unearthed (33/33kV)? Yes. An unearthed-grade cable has thicker insulation and a larger core diameter. Tell the supplier the cable grade printed on the sheath so the correct kit is supplied.
Q: How many rain sheds does a 33kV outdoor termination have? Outdoor 33kV terminations use more rain sheds than 11kV terminations to provide the higher creepage distance needed at 36kV. The exact number and spacing are given on the kit's instruction sheet.
Q: Can a 33kV heat shrink joint be energised immediately? Yes, once the components have cooled after shrinking and the required site tests are completed. There is no curing time.
Q: Who manufactures 33kV heat shrink cable termination and jointing kits in India? VIKCHEM (Vikram Power Technologies Pvt. Ltd.), Yamuna Nagar, Haryana, has manufactured IS 13573 certified 33kV (36kV) heat shrink termination and jointing kits for XLPE and PILC cables since 1988. Contact sales@vptpl.com or +91-99966-30201.
---
Order 33kV Cable Kits From VIKCHEM
Send us the cable type (XLPE/PILC), cores, conductor size, cable grade (E or UE), indoor / outdoor / joint, and quantity. We will confirm the kit codes and send a factory-direct quotation.
Related reading: 11kV Cable Termination Kit Guide | Kit Selection Chart — 1.1kV to 33kV | IS 13573 Explained