Why Cable Accessories Are the Hidden Critical Component in Solar Power Plants

India is building solar power faster than almost any other nation — over 100 GW installed and 500 GW targeted by 2030. Behind every solar module, inverter, and transformer in these projects is an extensive cable network, and connecting those cables safely and reliably requires one product category that EPC contractors often treat as an afterthought: cable accessories.

In solar power plants, a failed cable joint or a poorly installed termination kit does not just trip a circuit breaker. It creates an arc fault, a fire risk, or a sustained outage that erases months of energy production and triggers liquidated damages under the PPA. Cable failures at the LT and HT levels are among the top five causes of unplanned downtime in ground-mounted solar plants across India.

This guide covers everything EPC contractors and solar developers need to know about selecting, specifying, and sourcing cable accessories for Indian solar power projects.

VIKCHEM (Vikram Power Technologies Private Limited) has been supplying IS 13573 certified heat shrink termination kits, cable jointing kits, and power cable accessories to solar developers across India and 20+ countries since 1988. This guide is written from that operational experience.

---

Cable Systems in a Ground-Mounted Solar Power Plant

A typical ground-mounted solar plant has three distinct cable voltage levels, each requiring different accessories:

1. DC String Cables (Up to 1.5kV DC)

String cables run from solar module junction boxes to combiner boxes or string inverters. These use UV-resistant single-core PV cables (TUV-approved, H1Z2Z2-K or equivalent) terminated with MC4 connectors. At this level, the primary accessories are:

  • Copper cable lugs (correctly sized, crimped to manufacturer specification)
  • Heat shrink end caps on unused cable ends during construction
  • Heat shrink tubing for protecting spliced conductors at combiner boxes
  • 2. AC Cables — Inverter to Step-Up Transformer (415V)

    The inverter LV output connects to the step-up transformer via 415V XLPE cables. Accessories at this level:

  • Heat shrink indoor termination kits (1.1kV rated) at the transformer LV bushing and inverter output
  • Straight-through heat shrink jointing kits (1.1kV) for LT XLPE cable runs that must be spliced
  • Cable lugs for all LT terminations — copper or aluminium, sized to cable cross-section
  • Bus bar sleeves for busbar connections in the LV switchboard
  • 3. HT Underground Feeders (11kV, 22kV, or 33kV) — The Critical Level

    This is the most important cable level in a solar plant. Underground HT feeders carry bulk power from step-up transformers to the grid-interconnection pooling substation. These cables:

  • Are single-core or 3-core XLPE cables rated 11kV, 22kV, or 33kV
  • Run in cable trenches across the entire plant area — typically 2 to 10 km
  • Must be jointed wherever cable drum lengths are exceeded (every 400–600 m)
  • Require termination kits at the transformer HT bushing and at the pooling substation switchgear
  • Cable accessories required at HT level:

    |----------|-------------------|

    ---

    Selecting the Right Termination Kit by Voltage Level

    |---------------------|-----------|--------------|

    VIKCHEM's heat shrink cable termination kits cover every voltage from 1.1kV to 36kV, fully certified to IS 13573 and IEC 60502-4.

    Indoor vs Outdoor Termination Kits in Solar Plants

    Outdoor termination kits are required at:

  • Transformer HT bushing connections exposed to weather
  • Overhead line riser connections at the pooling substation fence
  • Outdoor ring main units (RMUs) and outdoor vacuum circuit breakers
  • Indoor termination kits are required at:

  • 11kV/33kV switchgear cubicles inside the pooling substation control room
  • GIS (Gas Insulated Switchgear) panels where the cable terminates in an SF6 or dry-air enclosure
  • VIKCHEM outdoor termination kits include stress-control tubing, phase-colour coded mastic sealing, multi-skirt rain sheds, and UV-stabilised outer jackets — all rated for India's tropical humidity and temperature cycling.

    ---

    Heat Shrink vs Cold Shrink for Solar Projects

    Both technologies are used in solar projects, but heat shrink dominates for good reason:

    Heat shrink cable accessories are preferred because:

  • Shelf life is 10+ years (cold shrink retains spring-memory deformation over time in storage)
  • Performance is not sensitive to cable diameter variation — the tube shrinks down to fit
  • No risk of cold shrink core removal going wrong in field conditions
  • IS 13573 certified heat shrink accessories are widely stocked and competitively priced in India
  • Better suited to India's supply chain and installer training base
  • Where cold shrink may be chosen:

  • Confined space switchgear cubicles where a heat gun cannot be safely operated
  • Environments where an open flame or hot air is a fire hazard (solvent storage areas)
  • For most solar plant applications — outdoor transformer terminations, underground joints, and indoor switchgear — IS 13573 certified heat shrink cable accessories from VIKCHEM are the correct specification.

    ---

    Common Cable Accessory Failures in Solar Power Plants

    Understanding failure modes helps engineers specify and install accessories correctly:

    1. Moisture Ingress at Cable Joints

    The most common and most destructive failure mode. Groundwater migrates into the cable cut-end via the insulation screen, tracks along the joint interface, and causes progressive dielectric breakdown. This eventually results in a phase-to-earth fault or phase-to-phase fault, tripping the HT feeder.

    Prevention: Properly installed heat shrink joints with waterproof end caps, correct heat gun application (270°C–300°C), and IR test (1000V Megger minimum, 2500V preferred) before backfilling every joint.

    2. Incorrect Stress Control at Terminations

    At HT cable terminations, the electric field concentrates at the cable screen cut point. Without a properly positioned stress-control tube — which is integral in every IS 13573 certified kit — partial discharge initiates at the screen edge and the insulation degrades irreversibly over months or years before the eventual flashover.

    This is the primary reason why using non-certified or uncertified "economy" cable accessories is a false economy. The cost of a single feeder outage (lost generation, repair labour, crane hire, cable replacement) far exceeds the price premium for certified accessories.

    3. Incorrect Cable Preparation

    The top three installation errors that defeat even high-quality accessories:

  • Incorrect screen cut position (screen left too long or cut too short)
  • Insulation surface not adequately cleaned and primed before shrinking
  • Wrong crimp die used for the cable lug — resulting in a cold crimp with high contact resistance
  • Solution: VIKCHEM's accessory kits include step-by-step pictorial installation instructions in English and Hindi, with explicit dimensions for each voltage class and cable size.

    4. Thermal Overload at Peak Generation

    Solar plants carry peak HT feeder current during the midday generation window (typically 11:00–14:00 IST). If cables are undersized or joints are installed in poorly ventilated or flooded trenches with high thermal resistance, conductor temperature can exceed the cable's rated limit (90°C for XLPE). Sustained overtemperature accelerates insulation ageing by a factor of 2 for every 8–10°C above rating (Arrhenius law).

    Prevention: Thermal rating calculations should include derating for ground temperature, burial depth, grouping factor, and soil thermal resistivity — especially in sandy or dry-soil sites in Rajasthan and Gujarat.

    ---

    Standards Indian Solar Projects Must Specify

    |----------|-------|
    LocationRequired Accessory
    Mid-run cable jointStraight-through heat shrink cable jointing kit
    Transformer HT bushing (outdoor)Outdoor heat shrink cable termination kit
    Indoor switchgear cubicleIndoor heat shrink cable termination kit
    3-core to single-core breakoutHeat shrink cable breakout kit
    All HT lugsHeavy-duty copper/aluminium cable lugs
    Solar Plant VoltageCable TypeRequired Kit
    415V AC (LV)3-core or 4-core XLPE1.1kV indoor heat shrink termination kit
    11kV ACSingle-core or 3-core XLPE11kV heat shrink termination kit (IS 13573)
    22kV ACSingle-core or 3-core XLPE22kV heat shrink termination kit (IS 13573)
    33kV ACSingle-core or 3-core XLPE33kV heat shrink termination kit (IS 13573)
    StandardScope
    IS 13573Heat shrink cable accessories for 1.1kV–33kV XLPE/PVC cables — mandatory BIS standard for Indian grid-connected projects
    IEC 60502-4International equivalent, cited in ISTS-connected projects, World Bank/ADB-financed projects, and export markets
    IS 7098 (Part 2)XLPE cables specification — the cable accessory must be compatible with the cable design
    CEA Technical StandardsCentral Electricity Authority regulations for grid-connected solar plants specify approved makes and IS certifications
    > Important: A supplier can claim IS 13573 compliance without holding a valid BIS licence. Always ask for the BIS licence number and verify it on the BIS portal (www.bis.gov.in). Confirm the licence covers the applicable voltage class — a manufacturer licensed for 11kV is not automatically licensed for 33kV.

    ---

    Procurement Checklist for Solar Plant Cable Accessories

    Use this when procuring cable accessories for your next solar project:

    Specification Stage:

  • Identify all cable voltage levels in the BoQ (1.1kV DC, 415V AC, 11/22/33kV HT)
  • Write "IS 13573 certified" or "IEC 60502-4 certified" explicitly on tender documents and purchase orders
  • Specify cable cross-section (mm²) and conductor material (Cu or Al) for each circuit — kits are size-specific
  • Require manufacturer to submit BIS licence copy and type test reports with the bid
  • Evaluation Stage:

  • Verify BIS licence number on the BIS website; confirm voltage class and licence expiry date
  • Check that type test reports are for the same product, issued by NABL-accredited laboratory
  • Confirm lead time against your project commissioning timeline — critical accessories should not be on a 6-week import lead time
  • Installation Stage:

  • Ensure cable joints are made by qualified jointers (relevant trade certificate or factory training)
  • Check heat gun calibration — insufficient temperature causes incomplete shrinkage and voids
  • Perform IR test (Megger test) on every joint before backfilling the cable trench
  • Keep a signed joint record sheet for each joint (location, jointer name, test result, date)
  • ---

    VIKCHEM Cable Accessories for Solar Power Projects

    VIKCHEM supplies a complete range of IS 13573 and IEC 60502-4 certified cable accessories specifically suitable for Indian solar power plants:

  • Heat Shrink Cable Termination Kits — 1.1kV to 36kV, indoor and outdoor, single-core and 3-core, for XLPE and PILC cables
  • Heat Shrink Cable Jointing Kits — 1.1kV to 36kV straight-through and transition joints for XLPE cables
  • Power Cable Accessories — Cable lugs, ferrules, heat shrink tubing, bus bar sleeves, end caps, and mastic sealing tapes
  • Touch Proof Termination Kits — 11kV to 36kV elbow connectors for compact switchgear and ring main units used at solar pooling substations
  • All products are manufactured at our ISO 9001:2015 / ISO 14001:2015 / ISO 45001:2018 certified factory in Yamuna Nagar, Haryana, and carry ZeD Gold certification — India's highest manufacturing quality recognition.

    For solar project-specific quotations, technical data sheets, or installation support, contact VIKCHEM:

  • Email: sales@vptpl.com
  • Phone: +91-99966-30201
  • Website: www.vptpl.com
---

Related reading: IS 13573: India's Cable Accessory Quality Standard | Heat Shrink vs Cold Shrink Cable Accessories | XLPE Cable Jointing Procedure