Technical Guide12 min read

Cable Termination & Jointing Kit Selection Chart: Choose the Right Heat Shrink Kit by Voltage, Cores and Cable Size (1.1kV to 33kV)

By VIKCHEM Engineering Team•
Cable Termination & Jointing Kit Selection Chart: Choose the Right Heat Shrink Kit by Voltage, Cores and Cable Size (1.1kV to 33kV)

Which heat shrink termination or straight-through joint kit fits your cable? Use this selection chart to match voltage (1.1kV, 11kV, 22kV, 33kV), cable type (XLPE, PILC, transition), cores (1C or 3C) and conductor size in sq mm to the exact VIKCHEM kit code — with a 5-step checklist, common ordering mistakes and FAQs.

Quick Answer: How Do You Select a Heat Shrink Cable Kit?

To select the right heat shrink cable termination or jointing kit, match five things printed on or known about your cable:

  • ●Voltage grade — 1.1kV (LT), 11kV, 22kV or 33kV
  • ●Cable insulation type — XLPE, PILC, or XLPE-to-PILC (transition joint)
  • ●Number of cores — single core (1C) or three core (3C; for LT also 3.5C and 4C)
  • ●Conductor cross-section — in sq mm, e.g. 3 × 240 sq mm
  • ●Application — indoor termination, outdoor termination, or straight-through joint (STJ)
  • Each combination maps to one kit code. For example, an 11kV 3-core XLPE cable of 240 sq mm terminated inside a panel needs kit VXI-13; the same cable on an outdoor pole needs VXO-13, and a joint between two such cables needs VXS-13. The full charts are below.

    Vikram Power Technologies Pvt. Ltd. (VIKCHEM), Yamuna Nagar, Haryana, has manufactured IS 13573 certified heat shrink cable termination kits and cable jointing kits since 1988. This guide is written by our engineering team for site engineers, EPC contractors and procurement teams who need to order the correct kit the first time.

    ---

    How to Read a VIKCHEM Kit Code

    Every VIKCHEM kit code tells you exactly what the kit is for. Once you know the pattern, you can decode any code in our range.

    Code partMeaningExample
    VVIKCHEMVXI-13
    X / PCable type: X = XLPE, P = PILCVXI-13 = XLPE
    I / O / SApplication: I = Indoor termination, O = Outdoor termination, S = Straight-through jointVXI-13 = Indoor
    Extra SSingle-core (1C) cable kitVXIS-13 = 1C indoor
    First digitVoltage class: 1 = 11kV, 2 = 22kV, 3 = 33kVVXI-13 = 11kV
    Second digitConductor size band (see charts)VXI-13 = 3 × 240–300 sq mm
    VTSJ / VTSSJXLPE-to-PILC transition joint: 3-core / single-coreVTSJ-12
    VLT…1.1kV LT kits (T = termination, S = straight joint)VLTT-05

    ---

    11kV Heat Shrink Kit Selection Chart (XLPE and PILC)

    11kV is the most common distribution voltage in India, used by every state DISCOM for urban and rural feeders, RMUs and distribution transformers.

    11kV XLPE Cable — Three Core (3C)

    Cable Size (sq mm)Indoor TerminationOutdoor TerminationStraight-Through Joint
    3 × 16 – 95VXI-11VXO-11VXS-11
    3 × 120 – 185VXI-12VXO-12VXS-12
    3 × 240 – 300VXI-13VXO-13VXS-13
    3 × 400VXI-14VXO-14VXS-14
    3 × 500 – 630VXI-15VXO-15VXS-15

    11kV XLPE Cable — Single Core (1C)

    Cable Size (sq mm)Indoor TerminationOutdoor TerminationStraight-Through Joint
    1 × 16 – 95VXIS-11VXOS-11VXSS-11
    1 × 120 – 300VXIS-12VXOS-12VXSS-12
    1 × 400VXIS-13VXOS-13VXSS-13
    1 × 500 – 630VXIS-14VXOS-14VXSS-14
    1 × 800 – 1200VXIS-15VXOS-15VXSS-15

    11kV PILC Cable — Three Core (3C)

    Cable Size (sq mm)Indoor TerminationOutdoor TerminationStraight-Through Joint
    3 × 16 – 95VPI-11VPO-11VPS-11
    3 × 120 – 185VPI-12VPO-12VPS-12
    3 × 240 – 300VPI-13VPO-13VPS-13
    3 × 400VPI-14VPO-14VPS-14

    11kV PILC Cable — Single Core (1C)

    Cable Size (sq mm)Indoor TerminationOutdoor TerminationStraight-Through Joint
    1 × 16 – 95VPIS-11VPOS-11VPSS-11
    1 × 120 – 300VPIS-12VPOS-12VPSS-12
    1 × 400VPIS-13VPOS-13VPSS-13
    1 × 500 – 630VPIS-14VPOS-14VPSS-14
    1 × 800 – 1200VPIS-15VPOS-15VPSS-15

    ---

    22kV Heat Shrink Kit Selection Chart

    22kV networks are common in Maharashtra, Tamil Nadu and several industrial and metro-rail projects. The size bands match 11kV; only the voltage digit changes from 1 to 2.

    22kV XLPE Cable

    Cable Size (sq mm)Indoor TerminationOutdoor TerminationStraight-Through Joint
    3 × 16 – 95VXI-21VXO-21VXS-21
    3 × 120 – 185VXI-22VXO-22VXS-22
    3 × 240 – 300VXI-23VXO-23VXS-23
    3 × 400VXI-24VXO-24VXS-24
    3 × 500 – 630VXI-25VXO-25VXS-25
    1 × 16 – 95VXIS-21VXOS-21VXSS-21
    1 × 120 – 300VXIS-22VXOS-22VXSS-22
    1 × 400VXIS-23VXOS-23VXSS-23
    1 × 500 – 630VXIS-24VXOS-24VXSS-24
    1 × 800 – 1200VXIS-25VXOS-25VXSS-25

    22kV PILC Cable

    Cable Size (sq mm)Indoor TerminationOutdoor TerminationStraight-Through Joint
    3 × 16 – 95VPI-21VPO-21VPS-21
    3 × 120 – 185VPI-22VPO-22VPS-22
    3 × 240 – 300VPI-23VPO-23VPS-23
    3 × 400VPI-24VPO-24VPS-24
    1 × 16 – 95VPIS-21VPOS-21VPSS-21
    1 × 120 – 300VPIS-22VPOS-22VPSS-22
    1 × 400VPIS-23VPOS-23VPSS-23
    1 × 500 – 630VPIS-24VPOS-24VPSS-24
    1 × 800 – 1200VPIS-25VPOS-25VPSS-25

    ---

    33kV Heat Shrink Kit Selection Chart

    33kV is used for sub-transmission between grid substations and 33/11kV substations, and for solar and wind plant evacuation. Note that 33kV size bands are different from 11kV and 22kV — always check the band before ordering. See also our 36kV heat shrinkable termination kit range.

    33kV XLPE Cable

    Cable Size (sq mm)Indoor TerminationOutdoor TerminationStraight-Through Joint
    3 × 70 – 95VXI-31VXO-31VXS-31
    3 × 120 – 150VXI-32VXO-32VXS-32
    3 × 185 – 300VXI-33VXO-33VXS-33
    3 × 400VXI-34VXO-34VXS-34
    3 × 500 – 630VXI-35VXO-35VXS-35
    1 × 35 – 50VXIS-31VXOS-31VXSS-31
    1 × 70 – 150VXIS-32VXOS-32VXSS-32
    1 × 185 – 300VXIS-33VXOS-33VXSS-33
    1 × 400VXIS-34VXOS-34VXSS-34
    1 × 500 – 630VXIS-35VXOS-35VXSS-35
    1 × 800 – 1200VXIS-36VXOS-36VXSS-36

    33kV PILC Cable

    Cable Size (sq mm)Indoor TerminationOutdoor TerminationStraight-Through Joint
    3 × 70 – 95VPI-31VPO-31VPS-31
    3 × 120 – 150VPI-32VPO-32VPS-32
    3 × 185 – 300VPI-33VPO-33VPS-33
    3 × 400VPI-34VPO-34VPS-34
    1 × 35 – 50VPIS-31VPOS-31VPSS-31
    1 × 70 – 150VPIS-32VPOS-32VPSS-32
    1 × 185 – 300VPIS-33VPOS-33VPSS-33
    1 × 400 – 630VPIS-34VPOS-34VPSS-34
    1 × 800 – 1200VPIS-35VPOS-35VPSS-35

    ---

    XLPE to PILC Transition Joint Selection Chart

    A transition joint connects a new XLPE cable to an existing paper-insulated (PILC) cable — common when older city networks in Kolkata, Mumbai, Chennai and Delhi are extended or repaired.

    Cable Size (sq mm)11kV22kV33kV
    3 × 16 – 95VTSJ-11VTSJ-21VTSJ-31
    3 × 120 – 185VTSJ-12VTSJ-22VTSJ-32
    3 × 240 – 300VTSJ-13VTSJ-23VTSJ-33
    3 × 400 – 500VTSJ-14VTSJ-24VTSJ-34
    1 × 16 – 95VTSSJ-11VTSSJ-21VTSSJ-31
    1 × 120 – 300VTSSJ-12VTSSJ-22VTSSJ-32
    1 × 400VTSSJ-13VTSSJ-23VTSSJ-33
    1 × 500 – 630VTSSJ-14VTSSJ-24VTSSJ-34
    1 × 800 – 1200VTSSJ-15VTSSJ-25VTSSJ-35

    ---

    1.1kV LT Heat Shrink Kit Selection Chart

    For low-voltage (1.1kV) cables, VIKCHEM supplies LT heat shrink termination kits and LT straight-through joint kits. The multi-core kits cover 3, 3.5 and 4 core cables.

    Cable Size (sq mm)3 / 3.5 / 4 Core Termination3 / 3.5 / 4 Core Joint1 Core Termination1 Core Joint
    6 – 16VLTT-01VLTS-01VLTST-01VLTSS-01
    25 – 50VLTT-02VLTS-02VLTST-02VLTSS-02
    70 – 120VLTT-03VLTS-03VLTST-03VLTSS-03
    150 – 185VLTT-04VLTS-04VLTST-04VLTSS-04
    240 – 300VLTT-05VLTS-05VLTST-05VLTSS-05
    400VLTT-06VLTS-06VLTST-06VLTSS-06
    500 – 630VLTT-07VLTS-07VLTST-07VLTSS-07
    1000VLTT-08VLTS-08VLTST-08VLTSS-08

    ---

    5-Step Checklist Before You Order a Cable Kit

    Step 1 — Read the cable sheath. The outer sheath is printed with the voltage grade, number of cores, conductor size and insulation type, for example "11kV (E) 3C × 240 sq mm XLPE". Copy this exactly into your enquiry.

    Step 2 — Confirm indoor or outdoor. An indoor termination is for cable ends inside switchgear, RMUs, panels and transformer cable boxes. An outdoor termination has rain sheds and UV-resistant, anti-tracking material for pole tops, outdoor transformer bushings and switchyards. Using an indoor kit outdoors is one of the most common causes of early tracking failures.

    Step 3 — Check the size band. Kits are designed for a range of conductor sizes. If your cable is at the edge of a band (for example 3 × 95 or 3 × 120 sq mm at 11kV), state the exact size so the right band is supplied.

    Step 4 — Plan lugs and connectors. Confirm the conductor material (copper or aluminium) and the bolt size at the equipment end. For joints, confirm the ferrule or connector type. VIKCHEM also supplies shear-head mechanical lugs and ferrules.

    Step 5 — Specify the standard and documents. For DISCOM and government projects, ask for IS 13573 compliant kits with type test reports and a guaranteed technical particulars (GTP) sheet. Read our IS 13573 guide for what to ask.

    ---

    6 Common Mistakes When Ordering Cable Termination and Joint Kits

  • ●Ordering by voltage only — "one 11kV kit" is not enough; size band and cores change the kit.
  • ●Mixing up XLPE and PILC — PILC kits include oil-barrier and stress-control components that XLPE kits do not need.
  • ●Assuming 33kV size bands match 11kV — they do not (for example, 33kV 3-core starts at 70 sq mm).
  • ●Using indoor terminations outdoors — leads to surface tracking and flashover in rain and pollution.
  • ●Forgetting transition joints — joining XLPE to PILC needs a dedicated transition kit, not a standard STJ.
  • ●Not ordering spare kits — for large projects, keep 5–10% spares for re-terminations and fault repairs.
  • ---

    Heat Shrink Termination vs Straight-Through Joint: What Is the Difference?

    A cable termination finishes the end of a cable so it can be connected to equipment such as switchgear, a transformer or an overhead line. A straight-through joint (STJ) connects two cable lengths end-to-end to make one continuous cable, for long runs or fault repairs. Both use heat shrink tubes, stress-control tubing and sealing mastic, but a joint also restores the cable's screen, armour and outer sheath across the connection. For a full comparison of technologies, see heat shrink vs cold shrink cable accessories, and for installation see our XLPE cable jointing procedure.

    ---

    Frequently Asked Questions

    Q: Which kit do I need for an 11kV 3 core 240 sq mm XLPE cable? For an 11kV 3-core 240 sq mm XLPE cable, use VXI-13 for an indoor termination, VXO-13 for an outdoor termination and VXS-13 for a straight-through joint. All three cover the 3 × 240 to 300 sq mm band.

    Q: Which kit do I need for a 33kV single core 300 sq mm XLPE cable? Use VXIS-33 (indoor termination), VXOS-33 (outdoor termination) or VXSS-33 (straight-through joint). These cover the 33kV single-core 185 to 300 sq mm band.

    Q: Can one heat shrink kit cover more than one cable size? Yes. Each heat shrink kit covers a band of conductor sizes, because heat shrink tubes shrink over a wide diameter range. For example, the 11kV kit VXI-11 covers 3-core cables from 16 to 95 sq mm.

    Q: What is the difference between an indoor and an outdoor cable termination kit? An outdoor termination has rain sheds and UV-stabilised, anti-tracking material to withstand rain, sunlight and pollution. An indoor termination is shorter and designed for clean, dry enclosures such as switchgear panels and RMUs.

    Q: Do I need a different kit for PILC cable? Yes. PILC (paper insulated lead covered) cables need PILC-specific kits (codes starting with VP) that seal the oil-impregnated paper insulation. To connect XLPE to PILC, use a transition joint (VTSJ or VTSSJ).

    Q: Are VIKCHEM heat shrink kits IS 13573 certified? Yes. VIKCHEM manufactures heat shrink cable termination and jointing kits to IS 13573 for 1.1kV to 33kV cables, and supplies Indian DISCOMs, Railways, NTPC, BHEL, L&T and EPC contractors.

    Q: How do I get a price for a heat shrink cable kit? Send the cable details (voltage, cores, size, XLPE/PILC, indoor/outdoor/joint) and quantity to sales@vptpl.com or call +91-99966-30201. VIKCHEM replies with a quotation including the kit code, price and delivery time.

    ---

    Get the Right Kit, First Time

    Not sure which kit you need? Send us a photo of the cable sheath print and tell us where it will be installed — our engineers will confirm the kit code and send a quotation.

  • ●Heat Shrink Cable Termination Kits — 1.1kV to 33kV
  • ●Heat Shrink Cable Jointing Kits — Straight-Through and Transition
  • ●Contact VIKCHEM for a Quotation