Field Grading · 6.6kV–36kV

Heat Shrink Stress Control Tubing

Semi-conductive heat shrink tubing for electric field stress control at medium voltage cable terminations. Redistributes the concentrated electric field at the screen cutback point — preventing insulation breakdown at 6.6kV to 36kV.

Semi-ConductiveField Grading6.6kV–36kVIS 13573

Why Stress Control is Essential at Cable Terminations

In medium voltage cable terminations, cutting back the cable screen creates an abrupt end to the equipotential shielding layer. At this point, the electric field lines are forced to converge, creating a region of extremely high field intensity at the screen cutback edge. If left unmanaged, this field concentration causes partial discharge, surface tracking and eventual insulation breakdown — a leading cause of MV cable termination failure.

Heat shrink stress control tubing solves this problem by providing a controlled-resistivity path that redistributes the field lines over a longer distance, reducing peak field intensity below the breakdown threshold. VIKCHEM's stress control tubing is a mandatory component of all heat shrink termination kits for cable systems above 6.6kV, and is tested per IS 13573 and IEC 60502 type test protocols.

Technical Specifications

PropertyValue
Voltage Range6.6kV – 36kV
Tubing TypeResistive semi-conductive
Shrink Ratio3:1
Volume Resistivity10² – 10⁴ Ω·cm
Temperature Range-40°C to +130°C
StandardsIS 13573, IEC 60502

Installation

The stress control tube is positioned to overlap the cable screen cutback by the specified distance (as per kit instructions — typically 20–30mm), with the remainder extending onto the cable insulation. On heating, the tube shrinks uniformly and achieves intimate contact with the cable surface. The defined resistivity of the semi-conductive compound then redistributes the electric field over the overlap length.

Heat Shrink Stress Control Tubing – VIKCHEM
Download Brochure

Used In

  • All MV terminations above 6.6kV
  • XLPE and PILC cable terminations
  • Indoor switchgear terminations
  • Outdoor overhead cable ends
  • Transformer and RMU connections